The LMO... burner controls are designed for the start-up and supervision of single- or 2-stage forced draught oil burners in intermittent operation. · Forced draught oil burners conforming to EN 267 · LMO44... for stationary direct-fired air heaters · Burner controls for use with atomization oil burners of monoblock design conforming to EN 230 · Detection of undervoltages · Electrical remote reset · Contact for oil pre-heating · Monitoring of time for oil pre-heating · Accurate and reproducible program sequence thanks to digital signal handling · Controlled intermittent operation after 24 hours of continuous operation · Limitation of the number of repetitions · Multicolour indication of fault and status messages Yellow-burning flames are supervised with photoresistive detectors QRB..., blueburning flames with blue-flame detectors QRC...In terms of housing dimensions, electrical connections and flame detectors, the LMO...are identical to the LOA... oil burner controls. |